Located in an area with strong resistance
to natural disasters and equipped with cutting-edge
facilities, this is a large-scale suburban data center in the Kansai region.
The Sanda area is resistant to natural disasters and has good access from the central area of Osaka, making it a suitable location for data centers.
As a measure against lateral shaking, multiple seismic isolation devices are used for the foundation, and to counteract vertical shaking, critical vibration dampers (VEM dampers) that support each floor are adopted. The combination of these technologies can reduce earthquake shaking by up to 80%.
The power cables buried underground are fully redundant with two systems, allowing for maintenance and updates without interruption. The power receiving setup adopts a main and reserve line system that prevents outages even during maintenance. In the unlikely event that power supply stops, Uninterruptible Power Supplies (UPS) can provide power for about 10 minutes, during which time the in-house generator will start. Additionally, the air conditioning units also have dual power inputs, enabling continuous operation during inspections through system switching.
The UPS adopts a block redundant configuration with an N+1 setup for each UPS set, plus an additional N+1 as a common spare. In the event of a failure in the primary UPS, it is possible to switch automatically and instantaneously to the reserve UPS without any interruption.
The in-house generators installed inside the building are set up with an N+1 configuration of gas turbine generators, capable of continuous operation for 72 hours without refueling. Additionally, test operations are conducted once a month, and dummy load operations are carried out every six months.
The facility implements multi-layered security checks to enhance safety:
- 24-hour manned surveillance using cameras and security sensors
- Inspections of belongings using X-ray machines and metal detectors
- Prevention of unauthorized entry into server rooms or tailgating through personal identification using IC cards combined with biometric authentication systems
- Rack opening and condition monitoring with electronic lock systems
Server rooms provide space in units of over 450 square meters, and the environment can be customized to meet specific requirements. Within the free access area, sufficient height and space for power cables are secured, and by storing network cables in dedicated ladders above the racks, air conditioning flow can be efficiently directed to the racks.
※JDCC: Japan Data Center Council, a specified non-profit organization
※FISC: Financial Information System Center, a public interest incorporated foundation
※PCI SSC: Payment Card Industry Security Standards Council ※JEITA: Japan Electronics and Information Technology Industries Association, a general incorporated association
![]() |
![]() |
||
---|---|---|---|
Compliance Equipment Standards | Equivalent to JDCC Tier 4 | Equivalent to JDCC Tier 4 | |
Opening | 2008 | 2022 | |
Building | Total Floor Area | 22,173㎡ | 12,919㎡ |
Scale | 4 floors above ground, 1 basement level, and 2 floors of office building | 5 floors above ground, 1 basement level (including 3 floors dedicated to server rooms) | |
Structure | Reinforced concrete (RC) construction, seismic-resistant structure, floor seismic isolation, and rack seismic isolation | Steel frame construction, foundation seismic isolation + vertical vibration control | |
Power Equipment | Power Receiving Equipment | Special high-voltage reception at 77kV, with both main and reserve lines for power reception | Special high-voltage reception at 77kV, with both main and reserve lines for power reception |
Private Power Generator |
Gas turbine generator (capable of continuous operation for 72 hours without refueling) |
Gas turbine generator (capable of continuous operation for 72 hours without refueling) |
|
UPS |
Block redundant configuration (10 minutes compensation) |
Block redundant configuration (10 minutes compensation) |
|
Air Conditioning Equipment |
Water-cooled central air conditioning (N+2 redundant configuration) |
Water-cooled central air conditioning (N+2 redundant configuration) |